| Flamgard Fire Dampers

Flamgard fire dampers are designed to meet the highest
safety requirements and are accordingly approved by:

• Lloyds Register
of Shipping
• Det Norske Ventas (D.N.V.)
• Department of Trade (D.O.T.)
• Registro Italiano Navale (R.I.Na.)

Fitted to ventilation duct penetrations of fire and blast rated
divisions, a Flamgard fire damper will protect adjacent spaces
from the transfer of fire, explosive blast, or smoke ingress via
the ductwork system.

|
Size
Range
• 150 x 150 mm to 6000 x 6000 mm in
1mm increments duct width or height. Dampers larger than 2100
x 2100 mm comprise an assembly of dampers with individual control
boxes arranged to operate simultaneously from a single "hook-up"
connection.
*Standard
'Depth' of our Fire Dampers is 300mm
which cannot be modified due to our Fire Certification.

Construction
• Non corrosive stainless steel grade
304 or 316.
• Steel/stainless combinations available.
• Casing and blades: 3mm sheet material
• Blade Shaft: 25.4mm diameter
• Bearings: Oilite
• Seals: Closed cell meoprene
• Slide seal strips: 0.33mm (29 s.w.g.)
material
• Control Box: 2mm sheet material.

Design Features
All Dampers:
• Replaceable bearings.
• Opposed action multi-blade design (above 320mm duct height).
• Removable blades/replaceable side seals.
• Single thickness plate blade.
• Interlocking blade meshing seal.
• Stub type blade shafts.
• 300mm duct insertion length.
• Hydrocarbon fire rated
FD04 Additional Features
• High performance duct and blade seals (ceramic/st/st).
FD04/1 Additional Features
• As FD04 plus high performance bearing seals (ceramic/st/st).
• Manual, Electrical & Pneumatic Damper controls are
available.
*Please note Flamgard
standard flange drillings will be used, if any project standard
flange drillings are required please notify us*
For
our flange drilling data sheet > CLICK
HERE
|
|
-------------------------------------------------- |
Calidair
Fire Dampers

Flamgard-Calidair
types CFD-01, CFD-02 and CFD-C2
Fire dampers are fitted into ducting systems at the point the
ductwork penetrates a fire division within a building. The fire
damper is installed to maintain the integrity of the division at
the point of penetration and should have the same fire rating as
the division.
Key Features:
* Maximum 4 hour fire rating accordance with BS476 part 20 maximum module sizes
2100 mm x 2500 mm
• Low leakage in accordance with UL555S class 1
• Low pressure drop
• High temperature operation for smoke control.
• Designed to accommodate cyclic pressures
• Can be used as combined control and fire damper.
Data
Sheets:
CFD-01 - CLICK HERE
CFD-02 - CLICK HERE
CFD-C1 - CLICK HERE
|
Damper Specification:
The CFD range has been successfully tested in accordance with BS476 part 20
and IMO A754 and is certified by Lloyds and DNV for A0, A60 and H120 rated divisions.
A 4 hour fire rating has been achieved and operation up to 600 Deg C completed
for smoke control.
Design:
Parallel or opposed multi blade design with fabricated fully welded steel construction.
Damper Case:
The damper case is formed from 3.00 mm or 2.00mm thick sheet steel, fully welded
in either 316L, 304L stainless or galvanised mild steel. Special materials such
as 316TI can also be provided. Case depth is either 300 mm or 200 mm. Damper
units in excess of 1000 mm width are provided with a central mullion.
Flanges:
Standard 50mm drilled to suit the customer's specification, special flanges
can be provided.
Blades:
Double skin aerofoil section of 1.5 mm or 1.2 mm thick sheet
steel welded in either 316L, 304L stainless or galvanised mild steel. Special
materials such as 316TI can also be provided. Blades are of the Holden
firelock design having a three path labyrinth to produce a impenetrable fire
barrier.
Bearings:
Phosphor bronze Oilite.
Shafts:
19.05mm dia stainless steel shafts
Blade Side Seals:
316L Stainless steel
Linkage:
Stainless steel mounted on the outside of the damper case.
Lifting:
Lifting eyes or lugs can be provided
Actuation:
A wide choice of manual, pneumatic and electric actuators are available.
High Temperature Applications:
Suitable for high temperature operation for smoke clearance, electric
actuators are fitted with a thermal jacket for temperatures up to 400 Deg C
Options:
• CFD-C1 single blade circular dampers to suit circular ductwork
• Circular spigots
• Control packages
|
| Shut Off Dampers

Flamgard's Shut Off / Isolation dampers are designed
to provide low leakage levels when subjected to high static pressures.
The rigid twin skin trafford aerofoil blade design has enhanced
stiffness which permits individual blade lengths of 1200mm to
be used without the need for center mullions. Ideally suited for
fan shut-off duty, these dampers are often installed with vertical
blade axis when positioned directly at the discharge of a centrifugal
fan scroll, to minimise turbulence and pressure losses. Tolerant
of arduous duct conditions, these dampers perform with minimal
maintenance within hot gas airflow systems

|
Size
Range
• 150mm x 150mm to 5000mm x 5000mm.
• Dampers larger than 2500mm x 2500mm comprise an assembly
of dampers with individual control boxes arranged to operate
simultaneously from a single "hook-up" connection.

Construction
• Full stainless steel grade 304 or
316.
• Steel/stainless combinations available.
• Integrally formed flanges with casing.
• Casing: 3.0mm material
• Blades: 3.0mm and 2.0mm material
• Blade shafts: 25mm diameter
• Bearings: Oilite
• Seals: Closed cell meoprene
• Side seal strips: 0.33mm (29 s.w.g.) material.
• Control box: 2.0 material

Design Features
All Dampers:
• Replaceable bearings.
• Opposed action multi blade design (above 320mm duct height).
• Removable blades/replaceable seals.
• Stub type blade shafts.
• Twin skin trafford aerofoil blade form.
• 300mm duct insertion length.
SD04 Additional Features:
• High performance duct seals (ceramic/St/St).
SD04/1 Additional Features:
• As SD04 plus high performance bearing seals (ceramic/St/St).

Options
• Drilled or undrilled flanges.
• Circular duct adaptors.
• "Z Form" plate blades for parallel action.
• Pressure relief flap incorporation.
• Manual, Electrical & Pneumatic Damper controls are
available.
*Please note Flamgard
standard flange drillings will be used, if any project standard
flange drillings are required please notify us*
For
our flange drilling data sheet > CLICK
HERE
|
|
-------------------------------------------------- |
| Calidair
Heavy Duty Shut-Off Dampers

Flamgard-Calidair
types CCD-01 and CCD-02
Generally this type of damper is used to either balance or control the flow
of air through ducts. The final application of this type of damper will often
define the damper's description, these may include:
• Volume control
• balancing
• modulating
• shut-off
• smoke control
• bypass
• isolation.
The CCD -01 control damper is basically the same design as the CFD-01 fire damper
and shares many components. The only major difference is the Firelock blade
design of the CFD-01.
Data
Sheets:
CCD-01 - CLICK
HERE
CCD-02 - CLICK HERE
|
Damper Specification:
The CCD-01 has been specifically designed as a heavy-duty industrial damper
suitable for a wide range of applications. The type CCD-02 is more suited for
less onerous applications. Parallel or opposed multi blade design with fabricated
fully welded construction.
Damper Case:
The damper case is formed from 3.00 mm or 2.00mm thick sheet steel fully welded
in either 316L, 304L stainless or galvanised mild steel. Special materials such
as 316TI can also be provided. Case depth is either 300 mm or 200 mm.
Flanges:
Standard 50mm drilled to suit the customer's specification, special flanges
can be provided.
Blades:
Double skin aerofoil section of 2.00 mm, 1.5 mm or 1.2 mm thick sheet steel
welded in either 316L, 304L stainless or galvanised mild steel. Special materials
such as 316TI can also be provided. Blade edge seals may be fitted to reduce
damper leakage.
Bearings:
Phosphor bronze Oilite or roller type.
Shafts:
19.05mm dia stainless steel shafts.
Blade side seals:
Stainless steel.
Linkage:
Stainless steel mounted on the outside of the damper case.
Lifting:
Lifting eyes or lugs can be provided.
Actuation:
A wide choice of manual, pneumatic and electric actuators are available
(refer to actuator data sheet).
High temperature operation:
Suitable for high temperature operation for smoke clearance, electric actuators
are fitted with a thermal jacket for temperatures up to 400Deg C.
Options:
• CCD-C1 single blade circular dampers to suit circular ductwork
• Circular spigots
• Control packages
|
| Volume Control
Dampers

Flamgard's "20 Series" damper is a good
quality multipurpose product manufactured in a choice of materials
and damper drive/control combination. It is suitable for:
• Ductwork system balancing
• Airflow volume control
• Space pressure control
• Smoke/gas control
• Ductwork isolation
• Building services
• Light and medium industrial
ventilation
• Tunnel ventilation
• Marine
• Offshore petroleum.

|
Size
Range
• 150mm x 150mm to 4000mmx 4000mm.

Construction
• Full stainless steel grade 304 or
316.
• Steel/stainless combinations available.
• Integrally formed flanges with casing.
• Casing: 1.6, 2.0 or 3.0mm material
• Blades: 2.0mm material
• Shafts: 18mm diameter
• Side seal strips: 0.33mm (29 s.w.g.)
material.

Design Features
• Ability to fully dismantle.
• Opposed blade movement.
• Phosphor bronze replaceable bearings.
• Removable blades/ replaceable side seals.
• Single thickness formed plate blades.
• Interlocking blade meshing seal.
• Stub type blade shafts.
• 200mm minimum duct insertion length.

Options
• Drilled or undrilled flanges.
• Circular duct adaptors.
• Manual, Electrical & Pneumatic Damper controls are
available.
*Please note Flamgard
standard flange drillings will be used, if any project standard
flange drillings are required please notify us*
For
our flange drilling data sheet > CLICK
HERE |
| Pressure Control
Dampers

Flamgard's Pressure Relief and Non Return damper
products are identical dampers, each fitted with an adjustable
counterweight system to suit the individual application of each
product. Pressure relief dampers can be used as a static relief
flap for overpressure situations or in the dynamic control of
air pressure within a space or room. Non return dampers are used
to prevent recirculation or back-flow of ventilation air. Particularly
useful as a low cost solution to prevent air recirculation through
an idle standby fan of a duty and standby ventilation fan configuration.
Both styles of this improved damper design provide low leakage
performance on return airflow.

|
Size
Range
• 150mm x 150mm to 2000mmx 2000mm.

Construction
• Full stainless steel grade 304 or
316.
• Steel/stainless combinations available.
• Integrally formed flanges with casing.
• Casing: 3.0mm material.
• Blades: 1.2mm material.
• Shafts: 10mm diameter.
• Bearings: Oilite
• Seals: Closed cell neoprene.

Design Features
• Aerodynamic blades.
• Adjustable counterweight balancing system
• Low backflow leakage.
• Low pressure loss at low velocity.
• Linkage enclosure.

Options
• Pre-drilled or plain flanges.
• Left or right hand linkage enclosure (viewed facing airflow).
• Lighter gauge casing material.
• Mechanical blade position indicator.
• Manual, Electrical & Pneumatic Damper controls are
available.
*Please note Flamgard
standard flange drillings will be used, if any project standard
flange drillings are required please notify us*
For
our flange drilling data sheet > CLICK
HERE |
| Blast Dampers

Flamgard's Blast dampers 'BLD01' (1Bar)
& 'BLD-02' (0.4Bar) are designed to prevent
blast forces entering ventilation duct systems. They are rigidly
constructed for this purpose and comprises of two sections. An
'eggcrate' section directs the blast onto the blade pack, which
consequently closes under blast pressure, isolating the blast
force and preventing blast damage or loss. The blade open position
is adjusted and held by a 'blast break' mechanism.
|
Size
Range
• 300mm x 300mm to 3000mm x 1500mm.
*Please note smaller sizes can be accomodated with the use of
'transition ducts'.

Construction
• Full stainless steel grade 304 or
316.
• Steel/stainless combinations available.
• Casing: 5.0mm (minimum)
material
• Blades: 5.0mm (minimum)
material c/w blast lipped edges.
• Shafts: Stub type 25.4mm
diameter
• Bearings: Zeron

Design Features
• Opening position set at 45°
• Adjustable blast break set point.
• Low pressure drop.
• All component parts replaceable.

Options
• Pre-drilled or plain flanges.
• Left-hand or right-hand linkage enclosure.
• Heavyweight construction for large blast.
*Please note Flamgard
standard flange drillings will be used, if any project standard
flange drillings are required please notify us*
For
our flange drilling data sheet > CLICK
HERE
|
BLD-01
 |
BLD-02
 |
|
| Inlet Vane
Dampers

Flamgard's Inlet Vane dampers are rigidly designed
to meet the industry demands of zero downtime and low maintenance.The
use of I.V.D.'s at fan inlets saves energy in two ways:
1. At fan start-up a closed I.V.D. isolates fan
inlet, allowing the rotor to turn without air loading when at
speed the I.V.D. is opened.
2. During running the optimum angle setting of
the radial vanes causes the incoming air to 'swirl' in the running
direction of the turning fan rotor. |
Size
Range
• 300mm diameter to 2000mm diameter.

Construction
• Full stainless steel grade 304 or
316.
• Steel/stainless combinations available.
• Casing: 3.0mm material
• Blades: 3.0mm material.
• Shafts: 25.4mm diameter
• Bearings: Oilite
• Shaft Linkage: Rolled angel or channel
rings. Cast levers.
• Position lock: Slot and lock bolt design.

Design Features
• All damper parts are replaceable.
• Rack and pinion drive on larger duct sizes.

Options
• Pre-drilled or plain flanges.
• Auto control packages available.
*Please note Flamgard
standard flange drillings will be used, if any project standard
flange drillings are required please notify us*
For
our flange drilling data sheet > CLICK
HERE |
| Inert Gas
Dampers
Flamgard's Inert Gas Retention Damper is designed
retain Co2 or other inert gasses to extinguish fires in Gas
Turbine or other power generation installations. The Flamgard SD20
Damper has endured a severe testing programme by major Gas
Turbine manufacturers to prove its outstanding inert gas retention
capabilities . The Damper can be provided with a wide range of
pneumatic and electrical controls or with simple manual operation.
*Please
note Flamgard
standard flange drillings will be used, if any project standard
flange drillings are required please notify us*
For
our flange drilling data sheet > CLICK
HERE |
Size
Range
• 150mm x 150mm to 5000mmx 5000mm.

Construction
• Full stainless steel grade 304 or
316.
• Steel/stainless combinations available.
• Integrally formed flanges with casing.
• Casing: 1.6, 2.0 or 3.0mm material
• Blades: 2.0mm or 3mm material
• Shafts: 25.4mm diameter
• Side seal strips: 0.33mm (29 s.w.g.)
material.

Design Features
• Ability to fully dismantle.
• Parallel blade movement.
• Phosphor bronze replaceable bearings.
• Removable blades/ replaceable side seals.
• Single thickness formed plate blades.
• Special seal.
• Stub type blade shafts.
• 300mm duct insertion length standard, 200mm available
upon special request.
Options
• Drilled or undrilled flanges.
• Circular duct adaptors.
• Manual, Electrical & Pneumatic Damper controls are
available. |
|